The SICUROTRON LEJC series emergency lighting units, designed for VDE 0108 or EN 50172 compliance in continuous or standby modes, operate Power LEDs with NiCd battery backup. In mains mode, they regulate current (300 - 700 mA) for LEDs with voltage (5.6 V - 17.5V ≤350 mA or 5.6 V - 7.6 V >350 mA), capping mains power at 5 W. Emergency power is fixed at 0.8 W or 1.7 W. LEJC-S models include automatic self-tests every 30 days and an annual burn test, reporting errors until repair (LED status indicator).
SICUROTRON LEJC
Material
Housing: Polycarbonate
Details
Operating time: 3 h
Batteries: NiCd
Max. ambient temperature: 5 - 50 °C
Charging time: 24 h
Protection: IP 20 / Protection class I
Mains voltage: 230 V ±10 %
Mains frequency: 50 - 60 Hz
Consumption: max. 30 VA
Approval
Approval [pending]: CENELEC
Approved to: IEC 61347-2-7 | EN 61347-2-13 | EN 60598-2-22
General
SICUROTRON LEJC emergency lighting unit with an integrated driver, suitable for incorporation into luminaires for general lighting in safety luminaires with single batteries. For NiCd batteries.